標準防火工程

中文 EN

Buildings Department · BS 476 · BS EN 1634

A report is part of the door

Hong Kong practice followed British Standard BS 476. In 2011 the Buildings Department issued the Code of Practice for Fire Safety in Buildings. Buildings completed after that code follow BS EN 1634.

BS EN 1634 tests insulation and smoke control as well as fire integrity, so it is stricter than BS 476.

Five things, all of them

Integrity. For the rated time, the door must not deform in a way that lets flame through.

Insulation. The highest rise stays at or below ambient plus 180°C. The average rise stays at or below ambient plus 140°C.

Smoke control. The intumescent seal swells in heat and fills the gap between leaf and frame. A smoke seal on the frame holds the smoke.

Self-closing. A fire door has to shut itself in ordinary use.

A test report. No report, and the door is not compliant.

Questions

Which standard applies to a fire door in Hong Kong?

Older buildings follow BS 476. Buildings completed after the Buildings Department Code of Practice for Fire Safety in Buildings 2011 follow BS EN 1634.

How is BS EN 1634 different from BS 476?

BS EN 1634 also tests insulation and smoke control, so it is stricter than BS 476.

What does a compliant fire door need?

Integrity, insulation, smoke control, self-closing, and a test report.

What is integrity?

For the rated time, the leaf must not deform in a way that lets flame through.

What temperatures does insulation allow?

The highest rise is not more than ambient plus 180°C. The average rise is not more than ambient plus 140°C.

What stops the smoke?

An intumescent seal in the gap, plus a smoke seal on the frame.

Why must the door close by itself?

It has to shut on its own. A door left open does not stop fire or smoke.

Can you hand over a door without a test report?

No. Without a test report it is not a compliant fire door.

Which door is used for a flat entrance?

A timber fire door, single or double leaf. Industrial buildings often use the same timber doors.

Which door is used on a roof or a rear stair?

A stainless-steel fire door.

Which door is used in a mall?

A stainless-steel fire-glass door, in a one-hour or a two-hour rating.

What do you need for a quote?

A photo of the opening. The price follows the photo and the site measure.

How does the order run?

After you accept the price we take a 50% deposit, then measure on site, make the door, deliver it, and remove the old door and the debris.

Are measuring and removal inside the starting price?

No. Measuring, removal, debris, and carrying the door up stairs are each a line on the quote.

How many doors can one job include?

About 100 to 200 doors.

What are the starting prices?

A plain room door starts around HK$5,000. A flat entrance door starts around HK$8,800. A fire-glass door starts around HK$15,800. Other patterns are priced separately. The figure follows the photo and the measure.

WhatsApp a quote